Key Points and Precautions for the Purchase of Load Switch

2024-08-28 16:09:26

The load switch is mainly used to break and close the load current. The load switch can also be used in conjunction with a high-voltage fuse instead of a circuit breaker. Because load switches are easy to use and reasonable in price, load switches are widely used in 10kV distribution network systems. Reasonable selection of load switches in the design is of great significance to ensure the safe and reliable operation of the power grid.

1.Correct coordination of load switch and fuse

The fundamental difference between a load switch and a fuse is that the fuse has the ability to break short-circuit current, while the load switch is only used for switching the load current. It is generally believed that the load switch closes and divides the operating current, and the fuse breaks the short-circuit current. However, when a fault occurs, because the three-phase current is not necessarily the same, and the error allowed by the fuse, the fusing time difference between the three-phase fuse is inevitable. After the first phase removes the fault, if the load switch cannot interrupt the load current in time, Causes transfer current and two-phase operation, causing damage to the power receiving equipment. A fuse with a striker and a load switch with a trip device can solve the problem of lack of phase operation. When the fuse of the fuse melts, the load switch trip device is immediately disconnected under the operation of the striker. Manufacturers mostly use a four-bar linkage mechanism. When the load switch is closed, the closing and opening springs are stored at the same time. When the four-bar linkage mechanism passes the dead center, the energy of the closing spring is released and the switch performs the closing operation. The energy of the brake spring is still maintained by the half-shaft mechanism. Once the striker strikes, the half-shaft is disassembled, the energy of the opening spring is released, and the switch performs an opening operation. Therefore, in use, you must choose a fuse with a striker and a load switch with a mechanical trip device.

It should be pointed out that most of the fuses in use are used as backup protection fuses. This type of fuse has a minimum breaking current, which is 2.5 to 3 times the rated current of the fuse. When it is less than the breaking current, the backup fuse cannot Breaking this current is the difference between it and a full range fuse. The full range fuse can be reliably disconnected by any current between the melting of the melt and the rated breaking current (40kA), but it is expensive. When the fault current is less than the minimum breaking current of the backup fuse, although the fuse cannot be guaranteed to be broken, the fuse will blow, the impactor in its memory will be hit, and the impact load switch will be broken. For example, for a fuse with a rated current of 100A, its minimum breaking current is about 250-300A. In this current region, the fuse cannot be broken, but the fuse blows the striker and strikes the load switch to trip, breaking the current, such as The load switch of 600A can be used to break reliably.

The load switch-current-limiting fuse combination has good protection characteristics for the transformer, but only when the two are combined can it be effective.

The area a is the operating current range.I>InK, InK is the rated current of the combined electrical appliance. It is less than the rated current InHH of the fuse. This is because the temperature condition and heat loss dissipation of the fuse are limited when the fuse is installed, so that the combined electrical appliance cannot withstand the full current of the fuse. The rated current breaking of the combined electric appliance is completed by the load switch alone. The three load switches are opened at the same time, and the arc is extinguished at the same time.

Area b is the overload range InHH<I<3InHH, within this range, the fuse is subjected to overcurrent exceeding the rated current. Starting from about 2InHH, the melt acts, but the fuse cannot yet extinguish the arc, and the striker of the fuse is triggered, which causes the load switch to act, and the three-phase opens and extinguishes the arc. Here, the meaning of melt action is that all melts are broken at least in one place. That is to say, in the overload range, the three-phase load switch opens and extinguishes the arc.

Area b is the overload range InHH<I<3InHH, within this range, the fuse is subjected to overcurrent exceeding the rated current. Starting from about 2InHH, the melt acts, but the fuse cannot yet extinguish the arc, and the striker of the fuse is triggered, which causes the load switch to act, and the three-phase opens and extinguishes the arc. Here, the meaning of melt action is that all melts are broken at least in one place. That is to say, in the overload range, the three-phase load switch opens and extinguishes the arc.

The c area is the transfer current ITC range from about 3InHH, and the arc can also be extinguished after the fuse is activated. In a three-phase circuit, one phase of the three-phase fuse acts first, triggering the striker and extinguishing the arc. The load switch extinguishes the current in the other two phases, and the other two-phase fuses may also act, but the load switch sometimes moves faster. Therefore, in the current transfer area, the fuse and the load switch cooperate to complete the breaking task. The transfer current is the maximum current that the load switch can break under their respective power factors, and it is between 5InHH (small fuse) and 1.5InHH (large fuse).

Therefore, only the load switch and the fuse are matched properly, the combined electrical appliance can be broken: any load current of the rated breaking current of the load switch; any overcurrent of the rated short-circuit breaking current of the combined electrical appliance . That is to say, the load switch plus the fuse can undertake the breaking task between the working current and the full short circuit.

2. Impactor operation and transfer current

The current passing through the fuse and the fusing time have an inverse time characteristic, referred to as ampere-second characteristic. When an overcurrent occurs, the fuse will blow according to its ampere-second characteristic. The so-called transfer current means that one phase of the three-phase fuse is opened first, and the fusing time difference of the three-phase fuse is Dt. After the prime minister moves, the striker strikes out. At this time, it may appear that the other two-phase fuses have not yet been extinguished and broken, and the striker strikes to form a load switch to cut off the fault current. The breaking task that should have been borne by the fuse is now transferred. To the load switch. When the fuse and the load switch are switched off, the symmetrical current is called "transfer current". Obviously, the value of the transfer current is related to the ampere-second characteristic of the fuse and the fixed breaking time of the load switch. The transfer current value can be determined by referencing the IEC-420 standard. On the fuse-second characteristic time axis, take 0.9 times the load switch fixed time and make a parallel line, and the corresponding current value is the transfer current. For example, a certain vacuum load switch has an inherent breaking time of 28ms and is equipped with a 100A fuse. The transfer current is calculated to be 1880A according to law, and the load switch should be able to break this current. When the fault current exceeds the transfer current, it is broken by a fuse. In fact, the transfer current is a current area. Because there is a difference in the melting time between the three-phase fuses, there is a relative current difference, so it is a very small current area, and this area is the transfer current area. It can be seen that the good cooperation between the load switch and the fuse can break any current. Obviously, different rated currents of the fuse have different ampere-second characteristics, so different rated currents and the same load switch will have different transfer currents. The rated transfer current refers to the transfer current of the largest fuse that can be equipped. Attention should be paid to the selection of load switch.

3 shunt release operating power and transfer current

With the promotion of "few people on duty" and "unattended" in substations, in order to meet the basic requirements of remote operation of operating units, when selecting load switches, it is necessary to configure shunt releases for protection tripping, that is, pass through when overloaded. The relay protection method opens the load switch, and the fuse is only for short-circuit protection. The load switch in the combined electrical appliance is broken by the action of the shunt release, which is called the release operation. The time-current curve of the relay protection and the fuse will not be the same, and a cross point will inevitably occur when used together. The point of intersection between the action characteristic of the relay protection and the ampere-second characteristic of the fuse is called the "transfer current". In engineering, the method to determine the maximum transfer current according to IEC is: take the minimum opening time of the load switch on the time axis of the maximum arc front ampere-second characteristic of the fuse, plus the minimum operating time of the external relay protection of 20ms, and the corresponding current value is Maximum transfer current.

4 Selection of combined electrical appliances

When selecting a combined electrical appliance, the value of the transfer current or the transfer current of the selected load switch must be appropriate. The selection of the fuse should consider the rated current of the transformer, the overload factor is 1.5, the magnetizing inrush current is 12 times 0.1s, and the surrounding environmental factors. The load switch can be divided into gas production, compressed gas, SF6 and vacuum according to its arc extinguishing principle. The gas-producing switch glows from the arc extinguishing tube by the arc generated between the contacts of the opening, and generates gas to extinguish the arc. As the number of breaking times increases, the arc extinguishing tube gradually burns out, so the arc extinguishing tube must be replaced continuously. The gas-producing load switch can only break currents below 1000A. The compressed air switch relies on the gas generated during the opening movement of the movable contact rod to extinguish the arc. The movable contact rod is a hollow copper rod with a fixed piston built in, and the arc is extinguished by the gas generated during the opening movement. The approximate breaking current of the compressed air load switch is between 1350 and 1850A. A value below this range will greatly reduce the reliability of the product. The main advantage of the SF6 switch is three or four circuits. It is small in size and not affected by the external climate in the SF6 gas. However, SF6 gas consumes ozone resources and does not conform to the trend of environmental protection. Its current breaking capacity is between 2000~3500A. After 2000, the general user engineering design required the SF6 load switch to have zero gauge pressure and the ability to break the normal load, even when the SF6 gas leaks, it must have a certain load breaking ability. In 2000, the market used MINRONG/民Most of the melting production. It is difficult for the air and pressure type load switch to break the transfer current above 2000A, so it is recommended to use it in the project below the transformer capacity of 500kVA. For the transformer capacity above 500kVA, it is recommended to use the vacuum load switch. The vacuum load switch adopts a vacuum interrupter, and the static and dynamic contacts are in the interrupter. The vacuum interrupter has strong breaking capacity, stable performance, no fire and explosion hazard, and can be operated frequently, maintenance-free, and not only can be opened If the transfer current is interrupted, the transfer current can also be interrupted to reach more than 2880A. In addition, choose a vacuum interrupter with a larger breaking capacity, such as between 10 and 25kA, which is most suitable for use with inverse time protection. This kind of vacuum load switch with high breaking capacity and equivalent secondary protection can actually be used as an economical vacuum circuit breaker .

Through the analysis of the selection of load switches in the design of 10kV distribution network systems, it provides experience on how to select load switches reasonably in the 10kV distribution network to ensure the safe and reliable operation of the power grid.

Precautionsedit voice

A. For vertical installation, the switch frame, closing mechanism, cable sheath, and protective steel pipe should be reliably grounded (cannot be grounded in series).

B. Several times of no-load opening and closing operations should be carried out before operation. There is no jamming of each rotating part, the closing is in place, and there is sufficient safety distance after opening.

C. The fuse melt used in series with the load switch should be selected appropriately, that is, when the fault current is greater than the breaking capacity of the load switch, the melt should be guaranteed to fuse first, and then the load switch can be opened.

D. The contact is good when the switch is closed, and the connection part is not overheated. During the inspection, pay attention to check the porcelain bottle for dirt, cracks, porcelain falling, flicker and discharge; the switch cannot be flushed with water (indoor type). (When a high-voltage cabinet controls a transformer, it is better to shut down the circuit high-voltage cabinet when replacing the fuse.)

As one of the professional load switch manufacturers and suppliers in China, we are characterized by customized products and competitive prices. If you want to buy load switches, please ask our factory for price lists, quotations and free samples.

Since its establishment, our company has been committed to the research and development and production of high-performance vacuum circuit breakers, gas-filled cabinets, ring network cabinets and accessories, and has always maintained an unconventional and innovative development idea, and won the praise and trust of customers with excellent quality.

 

 

Send

You May Like

0